Project Profile:

Manufacturer Tank Lining and Insulation

Overview:

A 100-year family-owned window and door manufacturer commissioned TMI to complete a tank lining and tank insulation project.

A 100-year family-owned window and door manufacturer commissioned TMI Coatings, Inc. (TMI) to work on their indoor and outdoor tanks. TMI is to complete a tank lining and tank insulation project.

Outdoor Tank:

  1. TMI removed all existing sprayed-in-place urethane foam insulation for the outdoor tanks. This was challenging due to the adhesion of the old insulation to the steel tanks.
  2. TMI used partial containment to sandblast the carbon steel tank exteriors, eliminating the residual spray foam and preparing the steel to mitigate future corrosion.
  3. TMI applied one full coat of rust-inhibitive epoxy primer, providing robust corrosion protection beneath the newly installed sprayed-in-place urethane foam insulation.
  4. The newly applied sprayed-in-place urethane foam insulation was applied to the tank shell exteriors with an average thickness of three inches, contributing to reduced heating expenses.
  5. TMI coated the newly applied foam insulation with a protective material that offers excellent UV protection, thereby extending the insulation’s lifespan. This coating is designed to expand and contract without cracking, chipping, or peeling in response to temperature fluctuations and boasts outstanding color retention.

Indoor Tank:

  1. The owner thoroughly cleaned the tank interior, ensuring all residual products and contaminants were removed before TMI’s arrival.
  2. TMI sandblasted the interior of tanks to SSPC-SP5 White Metal Blast.
  3. After removing the spent abrasive, the tank interior underwent a thorough vacuum cleaning.
  4. TMI inspected the tank, checking for sharp edges, rough welds, and other imperfections.
  5. TMI applied the new tank lining, which is suitable and resistant to wood preservative mix per SDS.
  6. The tank lining was then baked to 200 F, despite the challenge posed by the owner’s sprinkler system, which required the owner to shut down production in the dip tank area for safety. This allowed TMI to force-cure the tank lining to the specified temperature for the environment.

tank lining and insulation

Outcome:

The window and door manufacturer now benefits from internal and external enhanced tank protection. TMI Coatings. Safety. Quality. On time. In that order.

With over 35 years of experience, TMI Coatings will have your project completed on time and within budget. Contact us today at 651-452-6100 for your free, no-obligation quote.